S1 Series

S1 Series

  • 46.2 to 63.0 MMBTU/hr
  • 1,100 to 1,500 HP
  • Gas, #2/#6 oil and combination
  • Available to <30 PPM NOx

 

The ProFire® S1 series burners use a true forced-draft design to deliver rated capacities against a wide range of furnace pressures.

  • C-B NT technology adaptable to all types of combustion chamber configurations
  • Top or bottom FGR connection option (LNS1 models only)
  • Air-atomizing, low-pressure oil nozzle with steam atomization optional
  • Parallel positioning is standard for optimal control throughout the firing range (NT models only)
  • Cam trim with 14-point adjustment range for consistent air/fuel ratios (S1/LNS1 models only)

 

The S1 series is suitable for firetube and watertube boiler applications. The standard S1 series offers natural gas, propane gas, air-atomized #2 or #6 oil and combination gas/oil fuel options from 46.2 to 63.0 MMBTU. The LNS1 series offers natural gas, propane gas, air-atomized #2 oil and combination gas/oil fuel options from 42.0 to 63.0 MMBTU to <30 ppm NOx. The NTS1 series offers natural gas, propane/air mix, air-atomized #2 oil and combination gas/oil fuel options from 33.0 to 63.0 MMBTU to <9 PPM NOxGas manifold on oil burners comes standard for easy upgrade to combination units. Easy access for maintenance is granted through hinged rear doors and burner access panels. A backward-curved impeller provides adequate combustion air for various furnace pressures. The FGR control valve insures proper metering of FGR for maximum NOx reduction; and the FGR shutoff valve is standard, which prevents combustible gases from returning to the combustion zone.

  • Process Steam
  • Industrial Process
  • Building Heat
  • Laundry and Dry Cleaning
  • Hospital and Healthcare
  • Emissions (ppm NOx)
    Uncontrolled
  • Fuel
    Gas, Oil, Comb.
  • Furnace Pressure
    8
  • Boiler Horsepower
    1,100 - 1,500
  • Input Capacity
    46,200 - 63,000
  • Min Gas Pressure
    9
  • Mode of Operation
    Full Modulation
  • Oil Input (US GPH)
    330 - 450
  • Parallel Positioning
    Standard
  • Turndown
    Up to 6:1

Discover More

Tundra sym 2

Education & Training

Cleaver-Brooks has a dedicated Training Department offering web-based programs, co-sponsored authorized representative regional programs, custom on-site programs at the customer’s facility, and programs held at Cleaver-Brooks facilities.

Learn More
thv_afmkt_Nov2012 (28)

Genuine Parts

Purchasing Cleaver-Brooks Genuine Parts is the best way to keep your boiler system operating at peak performance. Our parts are precision-engineered to fit your boiler, and they are rigorously tested for quality to ensure your boiler runs safely and reliably.

Shop Now
Mobile steam pic web small

Rental Solutions & Services

Our rental solutions provide for: capacity increases, peak demand, plant or steam outages, equipment shutdown due to inspection, retrofit or repair, and redundancy or disaster response contingency plans.

Learn More